Where to Put Grounding Bushings? 2023 NEC 252.92(B)

  Рет қаралды 22,640

Sparky Channel

Sparky Channel

9 ай бұрын

Also see: How to Bond Neutral and Ground With 2023 NEC Code Book and Handbook: • How to Bond Neutral an...
What's the Difference Between an EGC and a GEC?: • What's the Difference ...
Bonding Screws vs Bonding Straps (NEC 250.24 (B) Main Bonding Jumper: • Bonding Screws vs Bond...
NEC 2023: How to Find Torque Specs for Panels & Breakers Marked or Unmarked: • NEC 2023: How to Find ...
To enter next year's competition: www.idealind.c...
IDEAL TKO Carbide Tipped Hole Cutters Review: • IDEAL TKO Carbide Tipp...
IDEAL Electrical 30-3430 Smart-Grip - 9.5 in., Linesman Plier with New England Nose, Crimping Die, Fish Tape Puller: Amazon: amzn.to/3Qn1svJ
IDEAL INDUSTRIES 45-112 Forged Heavy-Duty Dual NM Wire Stripper: Amazon: amzn.to/3FG6xKD
IDEAL Electrical 35-426 Tongue & Groove Plier - 7 in. Steel Groove Joint Plier with Reinforced Flange, Straight Jaws, Dipped Handle: Amazon: amzn.to/3FFL18I
IDEAL INDUSTRIES Deadeye Magnetic Chip Collector: Amazon: amzn.to/40nMCcF
IDEAL 61-757 - 600A AC/DC TRMS TightSight Clamp Meter: Amazon: amzn.to/3L0utZr
IDEAL 61-747 TightSight 400 Amp 600-Volt Digital True rms AC/DC Clamp Meter: Amazon: amzn.to/45XprI9
IDEAL 64-415 200A AC/DC TRMS SplitJaw TightSight Meter w/Flashlight & NVCT: Amazon: amzn.to/3ZmUQ4B
Ideal 36-309 TKO Carbide Tipped Hole Cutter, 2": Amazon: amzn.to/46TDGy9
IDEAL INDUSTRIES INC. 36-311 TKO 4 Pcs Hole Cutter Kit - Carbide Hole Cutter Set, Smooth Start Pilot Bit, Carry Case: Amazon: amzn.to/3QHjYAc
As an Amazon Associate, I earn from qualifying purchases.
IDEAL Combination Drill Tap Kit 8pc. with SmoothStart Tips : Amazon: amzn.to/2pLDuyn I'll include a link for the 4pc. kit when it's available
IDEAL Grounding Pigtails with Ground Screws (Pack of 50): Amazon: amzn.to/2REz8pa
IDEAL 35-9305 Insulated Screwdriver Kit, 2 Piece: Amazon: amzn.to/2ysPCbv
IDEAL 61-534 Digital Circuit Breaker Finder with Digital Receiver and GFCI Circuit Tester: Amazon: amzn.to/2PYvR3p
Siemens HF324NR 200-Amp 3 Pole 240-volt 4 Wire Fused Heavy Duty Safety Switches: Amazon: amzn.to/3sqPAAC
Siemens SN4040B1200 SN Series 200 Amp Space 40-Circuit Main Breaker Plug-On Neutral Indoor Load Center, Grey: amzn.to/47hGuoC
Siemens SUAT111-0PQG Meter Socket with 4 Jaw, Ringless Cover, Horn Bypass, Overhead and Underground Feed, 135-Amp: Amazon: amzn.to/3safB7s
Cerrowire 147-1603BR 50-Feet 12/3 NM-B Solid with Ground Wire, Yellow: Amazon: amzn.to/45WElOf
IDEAL 35-741 Electrician's Champion 6-Piece Screwdriver Set: Amazon: amzn.to/2qGAlAh
Ideal Industries 35-936 Adjustable Torque Screwdriver: Amazon: amzn.to/2s1tsO1
Ideal 44-104 Wire Marker Booklets-Legend-46-90 10 each): Amazon: amzn.to/2KKcaes
IDEAL 35-238 Magnetic-Tip Measuring Tape, 30-Foot: Amazon: amzn.to/2E7HJwr
IDEAL 46-88 Black 8.5 Mil Wire Armour Heavy Vinyl Professional Electrical Tape: Amazon: amzn.to/2PzO0TA
IDEAL 4635 7 Mil Wire Armour Red Professional Vinyl Electrical Tape: Amazon: amzn.to/2rxAq9H
IDEAL 4635 7 Mil Wire Armour White Professional Vinyl Electrical Tape: Amazon: amzn.to/2LcZ090
IDEAL Website: idealnationals....
IDEAL 33-793 Compression Hip Kit: Amazon: amzn.to/2xedj4E
Ideal Industries 33-856 VDV Multimedia Cable Tester: Amazon: amzn.to/3bdvn49
Ideal Industries 33-866 Test-Tone-Trace VDV Tester Kit Network: Amazon: amzn.to/376evsF
VDV Multimedia Cable Tester Kit (33-856-A): Amazon: amzn.to/2SrrJe3
IDEAL 35743 Electrician's Champion 4-Piece Tool Kit: Amazon: amzn.to/2T1tVJ1
IDEAL Electrician's Champion 12-In-1 Screwdriver: idealnationals....
IDEAL 35-208 9" Torpedo Level: Amazon: amzn.to/2yA6y0q
Bill and sparkychannel.com are participants in the Amazon Services LLC Associates Program, an affiliate advertising program designed to provide a means for sites to earn advertising fees by advertising and linking to Amazon.com

Пікірлер: 59
@patrickkelley3408
@patrickkelley3408 9 ай бұрын
Thanks for stating it’s ok to exceed the code.
@SparkyChannel
@SparkyChannel 9 ай бұрын
No problem. Thanks Patrick!
@KC-op4ke
@KC-op4ke 9 ай бұрын
Code is a C, you can always do A+ level work.
@SparkyChannel
@SparkyChannel 8 ай бұрын
Good way to put it. @@KC-op4ke
@guillermojacques6671
@guillermojacques6671 9 ай бұрын
Always good information and thorough explanations on this channel.
@SparkyChannel
@SparkyChannel 9 ай бұрын
Much appreciated! Thanks!
@stillthakoolest
@stillthakoolest 9 ай бұрын
I think its important for people to think about what would happen in a fault condition and thatll help you make sense of it.
@SparkyChannel
@SparkyChannel 9 ай бұрын
Thanks!
@0786RICARDO
@0786RICARDO 19 күн бұрын
Service conduit in one end only 250v+ to ground on one end only, unless you don't have concentric knockouts when metal flex is used as EGC under allowed conditions When running a GEC or an electrode BJ in a ferrous conduit. It's required on both ends to nullify inductance
@steveloux4709
@steveloux4709 9 ай бұрын
Supply-side bonding jumper. Thanks Bill!
@SparkyChannel
@SparkyChannel 9 ай бұрын
Yes sir! Thanks!
@calebroskamp9937
@calebroskamp9937 7 ай бұрын
Good to have you back, Bill!
@thomasglessner6067
@thomasglessner6067 9 ай бұрын
Great teaching example. Thanks for all your hard work.
@SparkyChannel
@SparkyChannel 9 ай бұрын
Yes, I thought it would be because there seems to be a lot of confusion on the subject. Thanks so much!
@Eddy63
@Eddy63 9 ай бұрын
Good info as usual ... Thx Bill
@SparkyChannel
@SparkyChannel 9 ай бұрын
Thanks Eddy!
@calebmorand4604
@calebmorand4604 9 ай бұрын
I absolutely love these videos you make! Thank you for providing excellent information. Keep it up!
@SparkyChannel
@SparkyChannel 9 ай бұрын
My pleasure, thanks!
@Jason_Canada
@Jason_Canada 9 ай бұрын
🎉 i love this channel
@SparkyChannel
@SparkyChannel 9 ай бұрын
Great to hear! Have a great weekend!
@jrpritchard1622
@jrpritchard1622 9 ай бұрын
thanks Sparky for the great information and explain very helpful
@SparkyChannel
@SparkyChannel 9 ай бұрын
Glad to help!
@donl1410
@donl1410 9 ай бұрын
I was about to make a correction comment, but you updated your video accordingly. 🙂 (Without the bushing on the SEC nipple, the nipple would not be bonded.)
@SparkyChannel
@SparkyChannel 9 ай бұрын
LOL! I beat you to the correction this time. Yes, the nipple between the meter socket and the safety switch has to be bonded. I didn't realize that at first.
@donl1410
@donl1410 9 ай бұрын
👍😄@@SparkyChannel
@charliebrown325
@charliebrown325 7 ай бұрын
1000 thanks, you have grace for explaining grounding conductors cowboy....
@SparkyChannel
@SparkyChannel 7 ай бұрын
No problem, thanks!
@MrTooTechnical
@MrTooTechnical 9 ай бұрын
Kick ass
@SparkyChannel
@SparkyChannel 9 ай бұрын
Thanks Dave! Great to hear from you!
@TomCee53
@TomCee53 9 ай бұрын
I got this right because I recently had to add a grounding bushing at the incoming conduit of my service disconnect, which in my case is the circuit breaker panel.
@SparkyChannel
@SparkyChannel 9 ай бұрын
Good job Tom!
@MacCallumKipper
@MacCallumKipper 5 ай бұрын
Dude such a great channel!
@SparkyChannel
@SparkyChannel 3 ай бұрын
Glad you enjoy it!
@Weasel_NM575
@Weasel_NM575 9 ай бұрын
Here in New Mexico as long as rigid is used from penetration point from one panel to the next then we use ground bushing’s
@SparkyChannel
@SparkyChannel 9 ай бұрын
Sound's good!
@scottsullivan4354
@scottsullivan4354 8 ай бұрын
Excentric k/os, and service conduits 💯
@pheadland
@pheadland 9 ай бұрын
Feeling smug, because I guessed the correct location instinctively. Why did I jump straight to that? To me, it goes along with the rule about grounding the service disconnect itself. If that is the definitive local ground, it follows that it has to be where the ground is propagated to the conduit. But I'd install one on each side, because I want to be really, really sure no run of conduit can fry anyone under any circumstances, and $15 or so for an extra grounding bushing is cheap insurance.
@SparkyChannel
@SparkyChannel 9 ай бұрын
Great job! Yes, an extra grounding bushing is a great idea. The contestants only had one, so they had to really know their code.
@vicktorpatriot1430
@vicktorpatriot1430 5 ай бұрын
​@@SparkyChannel I guess with the meter base and that 3pole discount both having eccentric/ concentric knock outs how only one end of that nipple is required in the code to bonded and not both ends
@laynefournier4708
@laynefournier4708 4 ай бұрын
Do you feel extra smug because you had to let everyone know you guessed it right?
@gregchambers6100
@gregchambers6100 8 ай бұрын
Another reason I despise concentric knock outs.
@GypsyMoFoJoe
@GypsyMoFoJoe 3 ай бұрын
Your title show it as article NEC 252.92(B)
@ronaldkovacs7080
@ronaldkovacs7080 3 ай бұрын
I would be prone to putting a ground bushing on both sides of each conduit. Should a fault occur within any conduit the remaining knock outs in the hole may provide a poor electrical path and might result in a lot of arcing and possible fire hazard. Just my two cents, I realize it is not required less than 250 Volts.
@wizard3z868
@wizard3z868 9 ай бұрын
Im more knowledgeable than i thought i wld have put it whete you said made the most sense. Than i wld have liked to put one on the other enclosure line side
@SparkyChannel
@SparkyChannel 9 ай бұрын
Excellent! Yes, you could add more if you like.
@stillthakoolest
@stillthakoolest 9 ай бұрын
Good video. Say with a 480V circuit and you are leaving a bonded enclosure with EMT directly KO'd (no concentric or eccentric etc) going to a box WITH concentric KOs, a bond bushing would NOT be required as the conduit is properly bonded on one side, correct?
@ed6837
@ed6837 9 ай бұрын
On the line side of a service disconnect you still need to use a bond bushing under all circumstances I believe.
@stillthakoolest
@stillthakoolest 9 ай бұрын
@@ed6837 right. I wasnt clear but I was talking about a feeder or branch circuit at 480v
@SparkyChannel
@SparkyChannel 9 ай бұрын
See 2023 NEC 250.97 Bonding for Over 250 Volts to Ground
@KLAWNINETY
@KLAWNINETY 9 ай бұрын
I believe because it's 277/480 you have to have the grounding bushing no matter what for a service. (or other means listed in the next)
@googleuser1710
@googleuser1710 4 ай бұрын
what if you just ran a continuous unbroken ground wire from 2 ground rods through a lug connected to the bonded neutral in the meter socket to the ground bus on the next panel? Wouldn’t that effectively ground the entire system?
@ElectricianMagician
@ElectricianMagician 4 ай бұрын
You'd parallel the neutral....putting objectionable current on the housing of the panel, the disconnect, and the nipples.
@0786RICARDO
@0786RICARDO 19 күн бұрын
You're double dipping there, creating currents in the GEC
@0786RICARDO
@0786RICARDO 19 күн бұрын
​@@ElectricianMagicianyeah, grounding the meter is always a big mistake
@SteveN-sy4bm
@SteveN-sy4bm Ай бұрын
Where do you find the sizing of the actual jumper?
@AyAytch
@AyAytch Ай бұрын
Table 250.102 (C)(1)
@johncasor9698
@johncasor9698 8 ай бұрын
How could he miss that ?????????????
@SparkyChannel
@SparkyChannel 8 ай бұрын
Remember, these are apprentices. You can't except perfection. I would have loved to see 10 pros do this task and see if they all did it correctly. As I said in the video, I want Sparky Channel viewers to win contests like this! And just do it correctly in regular electrical work, of course.
@vicktorpatriot1430
@vicktorpatriot1430 5 ай бұрын
​@@SparkyChannel was this timed and the contestant just wasn't fast enough to finish?
Concentric and Eccentric Knockouts: Which Need Grounding Bushings?
8:37
How to Run Conduit in Studs per 2023 NEC 300.4(A)(1)
13:38
Sparky Channel
Рет қаралды 90 М.
ОБЯЗАТЕЛЬНО СОВЕРШАЙТЕ ДОБРО!❤❤❤
00:45
Meet the one boy from the Ronaldo edit in India
00:30
Younes Zarou
Рет қаралды 10 МЛН
小丑把天使丢游泳池里#short #angel #clown
00:15
Super Beauty team
Рет қаралды 36 МЛН
Вы чего бл….🤣🤣🙏🏽🙏🏽🙏🏽
00:18
Why Do We Bond at the Service Panel and Not a Subpanel?
19:46
Electrician U
Рет қаралды 1,2 МЛН
Kitchen islands and peninsulas in the 2023 National Electrical Code
17:14
What is the Difference Between Grounding, Bonding and Neutral?
15:15
Bonding, Metal Raceways [250.97, 2020 NEC]
7:00
MikeHoltNEC
Рет қаралды 19 М.
How to Bond Neutral and Ground With 2023  NEC Code Book and Handbook
7:08
U.K. Electrics SUCK! This is what we should be doing…🇫🇷
19:17
Artisan Electrics
Рет қаралды 183 М.
#1 DIY Electric Mistake - Can you use Romex Wire in Conduit?
3:44
Silver Cymbal
Рет қаралды 860 М.
Why Neutrals & Grounds are Connected in a Main Panel
20:13
Benjamin Sahlstrom
Рет қаралды 1,5 МЛН
ОБЯЗАТЕЛЬНО СОВЕРШАЙТЕ ДОБРО!❤❤❤
00:45