BAXI 105 Fault Finding diverter valves and hydroblock in a boiler - Gas Training

  Рет қаралды 43,921

Allen Hart

Allen Hart

Күн бұрын

How A Diverter Valve Works. Today we have an amazing training showing us how a Diverter Valve works on a combi boiler. Gas Training video.
Baxi 80 eco diverter valves and hydro block in a boiler
Baxi 80e diverter valves and hydro block in a boiler
Baxi 105e diverter valves and hydroblock in a boiler
Baxi 105HE diverter valves and hydroblock in a boiler
Potterton Performa 24 diverter valves and hydroblock in a boiler
Potterton Performa 28 diverter valves and hydroblock in a boiler
Potterton Performa 30 he diverter valves and hydroblock in a boiler
Main Combi 24 diverter valves and hydroblock in a boiler
Main Combi 24 he diverter valves and hydroblock in a boiler
Main Combi 30 he diverter valves and hydroblock in a boiler
Baxi Hydroblock diverter valves and hydroblock in a boiler

Пікірлер: 90
@jamesasprey2092
@jamesasprey2092 3 жыл бұрын
I could sit a listen to Roy talk about boilers all day the mans knowledge is second to none. What a asset he is to viva training!
@1000Zebedee
@1000Zebedee 5 ай бұрын
What a fantastic breakdown and explanation of how these parts interconnect in a combi boiler. Thanks for the video🙂
@supervitz7178
@supervitz7178 10 ай бұрын
Thanks to this video I have fixed our Main 24he. We bought a property with this old combi in and wanted to keep it going a bit longer before replacing with something more modern. Our boiler wouldn't fire unless there was a large amount of flow from the hot water taps, requiring two taps to be opened almost all the way for the diverter pin to fully extend and engage the microswitch. I had removed the diverter valve body and fully rebuilt it using a rebuilt kit from eBay, but this made no difference. Watching your video, I then discovered the hydraulic Venturi. This was an even bigger faff to remove, but eventually got there with a 24mm wrench. The plastic part had disintegrated and the spring was loose in the hydroblock. I fished it out and replaced it with a new £15 replacement from eBay and now the boiler works as intended. Surprisingly none of the gauze filters were blocked on this old boiler and everything was quite clean. I also removed the differential pipes and flushed them out with water and air. I have degrees in mechanical engineering and electrical engineering and currently work on designing building control systems, but I will be having a gas safe engineer come and check everything over before we move in to the property. Cheers.
@AllenHart999
@AllenHart999 10 ай бұрын
Thank You
@rocketman246
@rocketman246 2 жыл бұрын
Excellent video! Seemed like I’ve actually sat in the training classroom 😀
@kishore099
@kishore099 10 ай бұрын
Roy, you are a genius. 10/10. Not only an expert with vast experience, rare ability to explain and make it understandable to ordinary viewers. I know the video is for trainee engineers but ordinary householders can understand the workings and complexity of diverter valves.
@AllenHart999
@AllenHart999 10 ай бұрын
Thank You
@chrisgibson5803
@chrisgibson5803 3 жыл бұрын
Allan you’re a step ahead with the training. I hope you get recognition for your efforts. Best of luck pal.
@paulcopland6678
@paulcopland6678 3 жыл бұрын
One of the best explanations i have seen Roy..keep it up Allan
@bobbojones8157
@bobbojones8157 8 ай бұрын
I’m in awe of your knowledge . When I was working combi boilers only came in half way through my career they were and still are more trouble than they are worth just so many things that can cause problems
@markm49
@markm49 3 жыл бұрын
Love the 105 - so simple to service.
@StuHNomadBiker
@StuHNomadBiker 2 жыл бұрын
Brilliant video, I'm a breakdown engineer and learned a couple of things here 👍
@suheilhanna873
@suheilhanna873 3 жыл бұрын
As usual, 💫💫💫💫💫 can't find better teaching than this 🌹
@tonyfleming2669
@tonyfleming2669 10 ай бұрын
Very useful suggestion on ensuring the small pipe off the rear mounted bypass which feeds the pump proving diaphragm and associated microswitch isn't blocked. Great video.
@AllenHart999
@AllenHart999 10 ай бұрын
Thank You
@Timetochange76
@Timetochange76 3 жыл бұрын
You talk a language I understand. Great video and thanks doing it. I just wish I watched it before I spent hours repairing a main 24 he yesterday....it would of saved me a lot of time. ☺
@kosalaperera1899
@kosalaperera1899 2 жыл бұрын
Thank you, Sirs. Both Allen and Roy. love every bit of it.
@dan123collins
@dan123collins 3 жыл бұрын
Brilliant Training Roy. Thanks for sharing Alan 👍
@michaelgreenhalgh8825
@michaelgreenhalgh8825 3 жыл бұрын
another great video Roy is a good lad had him train me when i went down to Baxi
@user-lu9qr5uo2d
@user-lu9qr5uo2d 9 ай бұрын
Thanks the filter in the return seems to solve my problems 👍
@themadhatter4761
@themadhatter4761 3 жыл бұрын
Fantastic video, great explanation of the operation, excellent. 👍👍👍👍🇬🇧
@thornhillplumbing
@thornhillplumbing 2 жыл бұрын
The hydraulic Venturi can be difficult to remove. You need a 24mm ring spanner and it helps to spray it with shock release spray if it is stiff to loosen it up so you don't round it off. If the plastic part has crumbled , you can get the pieces of plastic out by removing the plate and poking the plastic out from the back. Also check in the plate for pieces of the plastic.
@hardevgill2425
@hardevgill2425 6 ай бұрын
thanks you explain very good.
@craigpriest8661
@craigpriest8661 3 жыл бұрын
Brilliant video Roy. 👍
@davelaye7003
@davelaye7003 Жыл бұрын
great knoledge
@AllenHart999
@AllenHart999 9 ай бұрын
Thank You
@Asfiya67
@Asfiya67 2 жыл бұрын
thanks Alan and Roy very helpful video
@namesanmanname297
@namesanmanname297 2 жыл бұрын
Excellent video. Very good explanation.
@rickycunningham6368
@rickycunningham6368 3 жыл бұрын
another great video Alan. loving the channel and content its proper interesting your a top bloke mate
@manohardevgun6543
@manohardevgun6543 Жыл бұрын
Hi Allan you are great explaining in deep depth. on my Bexi duo tec it take long time to get hot water going when heating is off. what could be be the problem? manohar
@robertwhiteoak91
@robertwhiteoak91 Жыл бұрын
Found those filters on a potterton I believe it was... almost made me cry, I'd spent that much time messing about with other things 😄
@MobinC97
@MobinC97 3 жыл бұрын
Cracking video Allen cheers
@ashokrawal3820
@ashokrawal3820 3 жыл бұрын
Always great videos, Many thanks
@rodknee87
@rodknee87 3 жыл бұрын
Brilliant, loads of useful info, cheers
@gasfitter78
@gasfitter78 3 жыл бұрын
Great video again.
@Capitaldoc
@Capitaldoc 3 жыл бұрын
Mate you doing a great job. God bless
@TheCabbycol
@TheCabbycol 3 жыл бұрын
Another great video, keep them coming
@ismailcelikkol2975
@ismailcelikkol2975 2 жыл бұрын
Great video, fantastic. thank you for that splendid work sir.
@kevind7150
@kevind7150 3 жыл бұрын
The small O ring at the back of the differential valve some time leaks, also. There is, a new one in the service kit. Which is sometimes over looked!
@colin5064
@colin5064 2 жыл бұрын
Great video all the info and tips you require to know
@S.Hitchcock
@S.Hitchcock Жыл бұрын
Brilliant video. Very knowledgable. Can you give me some advice on my 105 please? The pressure keeps gradually rising. It doesn't rise when doing nothing. The flat plate has been renewed 6 month ago so isn't pinholed or shouldn't be.The ev is ok. The pressure rises each time hot water is used, so after a couple of days using hot water the pressure is right round and overflowing outside. Thanks. Hope I'm not in for a hefty repair bill😂
@AllenHart999
@AllenHart999 9 ай бұрын
Sounds like the boiler could do with a service and the expansion vessel checking. it may even need a new one. Thanks.
@sheriefgerges7789
@sheriefgerges7789 3 жыл бұрын
Great video I would like to ask it will part numbers for metal washer for thermistor, water flow restrictor
@efrygasservices6169
@efrygasservices6169 3 жыл бұрын
Cracking video here guys 👍
@robjenkins9450
@robjenkins9450 9 ай бұрын
Great explanation Roy. Would you happen to have a cutaway of a 105 Instant diverter valve. That would be equally useful.
@AllenHart999
@AllenHart999 9 ай бұрын
No, sorry
@rezuk1208
@rezuk1208 3 жыл бұрын
Thanks allen 🤩🤩🤩
@hazelbulgin638
@hazelbulgin638 3 жыл бұрын
Great video lots of good information again quality
@leaturk11
@leaturk11 3 жыл бұрын
Great training, thanks chaps.
@DD-eh9cp
@DD-eh9cp 5 ай бұрын
Could do with a breakdown of each of the service kits for this hydraulic section with part numbers. Any chance of revisiting this training video and adding them?
@rayc1503
@rayc1503 3 жыл бұрын
Excellent content Roy, Allen and viva training. I always felt that baxi got it wrong with the GA range boilers. I have a pet hate for them, dislike working on them.
@richardhodgson7443
@richardhodgson7443 3 жыл бұрын
Cracking video 👍
@kennyjohnson8609
@kennyjohnson8609 2 жыл бұрын
Great video as usual. Roy is the man on the 105’s. the brass washer for the thermistor instead of the fibre ones provided anyone know the part number for it?
@1Mattza
@1Mattza 2 жыл бұрын
Well done lads very informative, thank you 👍
@Hyde999100
@Hyde999100 3 жыл бұрын
Another good video.....Thanks Allen......U Dah Mannn !
@davesaxon7348
@davesaxon7348 2 жыл бұрын
Great video, well explained. Cheers
@davidharris8885
@davidharris8885 Жыл бұрын
Thank you 👍
@sudhiradhikari19
@sudhiradhikari19 3 жыл бұрын
Thank you very much.
@veronicahart450
@veronicahart450 3 жыл бұрын
Wonderful video
@tommyblackman7119
@tommyblackman7119 10 ай бұрын
Great video Allen and Roy, May I ask as Roy never mentioned it, what would cause the pin on top if the diverter valve not to fully retract after demand, I have an issue where after pump has stopped the pin is half way out and still engaging the micro switch Many thanks
@lucasdoesgaming66
@lucasdoesgaming66 9 ай бұрын
Dirt on the pin stops it sliding through the stuffing box
@rhodespcrhodespc5094
@rhodespcrhodespc5094 9 ай бұрын
HAVE THE SAME ISSUE, RE-GRASED THE PIN ..BUT STILL STICKS UP@@lucasdoesgaming66
@sir-dil-a-lot
@sir-dil-a-lot 3 жыл бұрын
Great video.
@medmtv3975
@medmtv3975 Жыл бұрын
I cleaned everything like new every piece is cleaned and waxed good water pressure the membrane is good but the hot water pin is not coming out to activate hot water mode with my hand it moves perfectly but with water the pin doesn't come out
@kckplumbingandheating
@kckplumbingandheating 3 жыл бұрын
Great vid 👍🏻
@user-zx2fn3vw3j
@user-zx2fn3vw3j 2 ай бұрын
Radiators are getting warm when hot tap is running main 30 He ?
@tommyblackman7119
@tommyblackman7119 3 жыл бұрын
Great in depth video and learning new things Love knowing how things work and the cut down parts so You can see inside Also I’ve changed a few diverter valves on these boiler an a few times I’ve had the orings on the bypass leak.. Tried replacing for one of my kit box but nothing near correct size, Baxi do sell them but they don’t give you the actual size of the orings . I found thus awkward as you cannot replace this oring because not knowing the size.. would Roy know the size of the bypass oring ? Thanks
@spartacus09ful
@spartacus09ful 2 жыл бұрын
What could be the culprit of the plunger not coming out enough of the pressure differential valve on the front of diverter valve for hot water. It comes out a little bit but not enough to activate the microswitch. The plunger and diagphram have been replaced with no avail. The hot water does work but only with the heating on.
@davideyre254
@davideyre254 Жыл бұрын
Hi Alan just been called out, heating not firing, pin not coming out of block, changed diaphragm, power off as system comes up to pressure pin comes out and makes contact on microswitch, asked everyone no recommendations, changed diverter valve system works everything fine now but why did pin come out after diaphragm changed
@cjfox7541
@cjfox7541 2 жыл бұрын
Hi great vidio. I have a baxi105e and had no hot water just change the heat exchanger and fab hot water. But one hour later no hot water. Any help would be appreciated cj
@rhodespcrhodespc5094
@rhodespcrhodespc5094 9 ай бұрын
ON THE BACK PART OF THE DIVERATOR IF THE PIN IS STAYING UP, THIS AFTER REPLACING A NEW DIVERATOR ON A BAXI 80 ECO...WHAT IS THE PROBLEM..THANKS
@Ace-xm9iq
@Ace-xm9iq 2 жыл бұрын
Great video 👍. Where can I find the list of part numbers?
@mikeystyz
@mikeystyz 3 жыл бұрын
Great video Allen thanks
@faizraouf9118
@faizraouf9118 Жыл бұрын
Hi there got a main combi 25 got a problem the pump proving pin is continuously up and runing the pump I have changed the diverter valve the whole part but got the same problem I hope u can give me some idea ?
@timewaster1959
@timewaster1959 Жыл бұрын
Why do I only get hot water when heating is also on .
@kevindownes7763
@kevindownes7763 Жыл бұрын
I have a Baxi Duo-tech 28 HE A. It’s working okay, no fault codes etc. Located in a downstairs utility room. It feeds the radiators upstairs and them drops down into the lounge and onto the hallway. All the radiator upstairs get hot and the hot water supply is fine. However the radiators in the lounge and hall do not get any heat. i’ve checked and there are no blockages. The boiler has just had the DIVERTER cartridge, motor and thermistor replaced. but this has mad no difference. Any ideas what could be causing theirs. The boiler has been installed for 11 years.
@sukbajwa
@sukbajwa 2 жыл бұрын
Thanks for the video Alan. Can I use a 14mm socket to get that dhw venturi out
@taze95
@taze95 2 жыл бұрын
Hi, have one at the moment, hot water is temperamental, but when there’s a call for hot water the pin on the heating side doesn’t retract, the pin on the water side comes out, Boiler fires up but hot to start then goes tepid, pin on heating stays engaged with micro switch, any idea please
@kopynd1
@kopynd1 2 жыл бұрын
so what is the problem if you only get tap hot water when the radiators are on
@colin5064
@colin5064 2 жыл бұрын
Hi, could you post the hydro inlet assembly filter and flow restrictor part number 12 L. As Baxi parts don't list this individually, only the full unit? MAIN 24HE HYDRAULIC INLET ASSEMBLY 248246. So how can just the required serviceable items be obtained?
@bahiaharjinder
@bahiaharjinder 3 жыл бұрын
Hi allen another great informative video throughly enjoying roys boiler training its very helpful, is it possible to do one on the hydro block for the baxi instant combi he version its the one where the expansion vessel is used for pre heat would be superb if you could thankyou
@andrewwhant1154
@andrewwhant1154 2 жыл бұрын
Hi , i have a Baxi 105 HE , had a problem for some time with only getting hot water if the mixer tap is turned on full on all taps and it takes about 1 minute to get hot, as soon as you reduce the tap the burner stops and cold water , could you advice on what the problem could be, the plumber has changed the diaghram on the diverter, he saying now the diverter is faulty, would appreciate your help, thanks
@supervitz7178
@supervitz7178 10 ай бұрын
Hi. Did you ever fix this problem? I have the same thing. Please let me know, thanks.
@janosgaborsalanczi4836
@janosgaborsalanczi4836 8 ай бұрын
Thanks the video, could you have me the spare part kit number?
@timgordon7107
@timgordon7107 2 жыл бұрын
Question ? Running hot water tap radiators getting warm what is this please
@ReleaseThaPressure
@ReleaseThaPressure 2 жыл бұрын
Likely diverter valve issue, I'm here watching this with the same problem.
@michaelvenus8539
@michaelvenus8539 Жыл бұрын
Is the rear plunger meant to come up when the DW plunger hits the switch?
@anthonyjackson979
@anthonyjackson979 Жыл бұрын
Did you find the answer mine is doing the same
@Mad4plumbing-ltd
@Mad4plumbing-ltd 3 жыл бұрын
👍😉
@colin5064
@colin5064 2 жыл бұрын
looks like the part numbers promised at 12.min 50 on the video never made it, rather disappointing guys
Live Fault Finding #12 - Faulty Baxi Diverter Cartridge
16:11
CP Utility Solutions
Рет қаралды 18 М.
Matching Picture Challenge with Alfredo Larin's family! 👍
00:37
BigSchool
Рет қаралды 47 МЛН
Oh No! My Doll Fell In The Dirt🤧💩
00:17
ToolTastic
Рет қаралды 10 МЛН
Whoa
01:00
Justin Flom
Рет қаралды 45 МЛН
Gas Training - Boiler Fault Finding - No Hot Water - Roy Fugler
23:43
Another house saved from a combi
9:47
Urban Plumbers
Рет қаралды 146 М.
A detailed look at diverter valves in a boiler - Part 1
5:32
Baxi - sustainable heating and hot water solutions
Рет қаралды 148 М.
Gas Training - Sequence of operation gas boiler - Fault Finding
17:56
BAXI 105E/HE LEAKING WATER - DIAPHRAGM CHANGE
7:01
Abu Samdani
Рет қаралды 20 М.
Matching Picture Challenge with Alfredo Larin's family! 👍
00:37
BigSchool
Рет қаралды 47 МЛН