Installation of a breaker hold down kit to meet NEC 408.36(D) code compliance.
NEC 408.36(D) - Plug-in-type overcurrent protection devices or plug-in type main lug assemblies that are back-fed and used to terminate field-installed ungrounded supply conductors shall be secured in place by an additional fastener that requires other than a pull to release the device from the mounting means on the panel.
Any other common mistakes that happen when installing a manual generator interlock transfer switch? Let me know in the comments below!
I have an Eaton CH plug-on neutral loadcenter which required a CHPHD hold down kit - www.homedepot.com/p/Eaton-CH-....
Hold down kits are brand and model specific, if you don't have the same panel, you most likely will need to get a different kit.