Leaking Worcester Greenstar Flow Sensor/ Adaptor. Heating geeks boiler repair

  Рет қаралды 85,510

HeatingGeek

HeatingGeek

5 жыл бұрын

A quick repair on a Worcester Greenstar.
Most engineers will have got this wrong the first time!! I know I did.
Turn up with a flow sensor and leave with your tail between your legs.
To support this content and get access to the PDF files to go with this training click here: / heatinggeeks
The PDFs for this video are not done yet!!! SOON.
Injector cleaning tool: rover.ebay.com/rover/1/710-534...
To support the channel and see the tools used day to day by me check out the links below:
1) CARHARTT Tool Roll amzn.to/2yGiexO
2) BAHCO Screwdriver with LED amzn.to/2Op5Ug1
2)BAHCO Screwdriver without LED amzn.to/2yEhLML
3)WERA Kraftform Kompakt Screwdriver amzn.to/2OnOe4K
4)WERA 0.8x4x100 Flat screwdriver amzn.to/2RNcpra
5) KNIPEX Alligator amzn.to/2RNctqU
5)KNIPEX Cobra amzn.to/2PA5YWY
same size as the alligator above just the “cobra” version
6)BAHCO Spanner amzn.to/2IW3iR8
6)BAHCO Spanner with slimline jaw amzn.to/2yHCq2i
7)CK Wire cutters amzn.to/2RP19dW
7)CK Wire cutters (shorter version) amzn.to/2OnJwnB
8)KNIPEX bent long nose pliers amzn.to/2IW9uZ3
9)TESTO 510 Digital U gauge amzn.to/2Cfz36a
9)TESTO Bluetooth U gauge amzn.to/2IW4t30
10)Mirror tool amzn.to/2OpKVKl
11)Cheap as chips pick set!!! amzn.to/2OpK10o
12)FLUKE alert volt stick amzn.to/2PxCYPF
13)MONUMENT Tailing Spanner amzn.to/2OrypK8
14)Tee Bar 4mm amzn.to/2yDPRAr
15)Tee bar 2mm amzn.to/2yzbjGA
16)Tee bar 2.5mm amzn.to/2OqqSvd
17)Full Tee bar set amzn.to/2yAoIyk
18)10mm ratchet spanner (flex head) amzn.to/2IWCoZ9
19)8mm ratchet spanner (flex head) amzn.to/2IUDZP5
20)14mm/15mm spanner amzn.to/2Aa6wgZ
21)BAHCO small spanner amzn.to/2RRkKKH
22)Cheap Lock knife amzn.to/2IWatZf
23)Sharpie amzn.to/2IVrxPk
24)Injector cleaning pins link coming soon. Review to follow.
25)Rothenberger 18” heavy-duty pipe wrench amzn.to/2ChkRd6
These are the heat duty ones I use.
26)Knipex (large) amzn.to/2OrgfIm
27)BAHCO 12” (not wide jaw) amzn.to/2Aatuob
28)Fluke 115 multimeter amzn.to/2OqaFpF
Drain down hose amzn.to/2RM4ZEN
Gas Tap Grease amzn.to/2SE0jRL
Led lights for the ​van. amzn.to/2Bh7RTQ
Fluke 101 multimeter amzn.to/2PoLP5g
Extech EX330 amzn.to/2AYq872
Silicone grease amzn.to/2Rnls4F
Fluke Twist Guard probes
amzn.to/2CfwCz4
Commando drills
amzn.to/2L5f50u
Weed Sprayer amzn.to/2Ryx1Hh
Large LDF amzn.to/2I0ss4d
NTC Clamps:
amzn.to/2GVUWL5

Пікірлер: 258
@leonardsmithfield9391
@leonardsmithfield9391 4 жыл бұрын
People like yourself deserve a medal and if by chance I ever meet you I’ll buy you a beer and shake your hand. Your video saved me a couple of hours of head scratching. Thanks buddy
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Thanks. I'm glad it helps. This catches everyone out the first time. :-)
@rwgasservices6764
@rwgasservices6764 3 жыл бұрын
Very good video. I changed one of these adaptors today for the first time and thanks to this I did not find it at all daunting. Thank you for sharing this. Rob RW Gas Services,Manchester
@geoffball5803
@geoffball5803 3 жыл бұрын
Brilliant vid, I had the same problem, couldn't believe when I took it apart the flow restrictor housing was disintergrated (took out with minimal force) with half of it left behind in the tube, shocking quality, your video was very helpful, it's now working like a dream, they really need to make more of their parts from metal
@HeatingGeek
@HeatingGeek Жыл бұрын
Worcester Cheese.
@MagicMags
@MagicMags 3 жыл бұрын
What a hero bloke for putting on such a detailed video!
@Lordyosch
@Lordyosch 3 жыл бұрын
Thanks for this video! We sprang a leak last weekend and it had got worse over the week. A friend shared a link to this video, I investigated and found that I had the same problem. £8 and a few days later my boiler is back in full operation with no leaks! Cheers!
@HeatingGeek
@HeatingGeek 6 ай бұрын
No problem.
@funmonsterUK
@funmonsterUK Жыл бұрын
Many thanks for this... i was able to order the part and sort out the leak i had with relative ease thanks to this excellent step by step vid. You sir are a Gent :)
@oztastic1
@oztastic1 4 жыл бұрын
excellent video, just done the repair after ordering the parts at a grand total of £11!! now I have spare spare o rings if anyone wants them!! Thanks man
@stevenpike5452
@stevenpike5452 4 жыл бұрын
Top bloke for sharing this, my cheese sensor like most completely turned to fondu. The only mistake I made was when I struggling to get the clip back in and realised that I was trying to fit 2 'O' rings between the flow turbine adapter and the flow sensor! Otherwise not too bad, the silicon grease helps to seat the adapter and there is a definite clunk when it's in place. Leak sorted and as per the commentary, the hot water seems to arrive faster at the tap due to the flow restrictor working properly.
@HeatingGeek
@HeatingGeek 4 жыл бұрын
mmmmmm cheese. :-)
@prayercircle2805
@prayercircle2805 2 жыл бұрын
Thank you so much I followed your instructions and now my boiler is working
@philmartin2053
@philmartin2053 3 жыл бұрын
“We’ll pretend the boiler wasn’t on the whole time” 😂 love that
@HeatingGeek
@HeatingGeek 6 ай бұрын
Yeah, whoops.... ;-) I didn't see this comment 2 year ago.
@keithmatthews9043
@keithmatthews9043 5 жыл бұрын
Hi heating geek Keith again with Worcester 28cdi have now replaced diverter valve and everything seams fine took 3 hours . Dismantled the old valve to see what problem was.turned out to be one of the small cir-clips on the diaphragm, the inner one, had broken off allowing the weeker small spring to hold out the rod onto the micro switch.again I thank you for your reassurance, and a merry Christmas
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Glad you got it sorted. Hopefully it will give you a good few more years of service. Good boilers but a pain to work on.
@goldgas1216
@goldgas1216 5 жыл бұрын
So common, love this fault. Small apprentice hands fit in there nicely for the clip/pin. Great vid!
@HeatingGeek
@HeatingGeek 4 жыл бұрын
I missed this comment. Sorry. :-)
@pagejamesuk
@pagejamesuk 4 жыл бұрын
Top tip for any newbies like me; the large o-ring on the adaptor needs to slide all the way over the (cheese) nut then over the plastic lip. I had it the nut side of the lip first try and so it would not click in to the housing; DOH. Managed the clip after ten attempts by pushing the copper and sensor part back and wiggling the long side of clip into the right side first which then helped getting it down and in on the left side. Unfortunately the grey wire other side of connector popped out so given sensor had no power the boiler did not provide hot tap water; obviously the job of the sensor to prevent a burnout if no water, so stripped bit of the outer doubles it up and pushed it back in; et voila hot tap water once again. Thanks for the video.
@ddoubledutch4783
@ddoubledutch4783 4 жыл бұрын
Top man. Great information and vid. Careful with your new screen fella👍🏽
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Long gone now. New phone better edits. :-)
@kevinschoales844
@kevinschoales844 Жыл бұрын
Great advice again Geek, we have many contract companies that can not find this leak = new boiler, well it is over 10 years old say Worc.
@Denis-oz1ji
@Denis-oz1ji 4 жыл бұрын
Excellent video really helped and yep it solved the problem, I was a bit baffled as the inner fixed section does not look like and engineered finish, it looked like remnants of the broken part until I re-watched you video and saw yours was the same. Many thanks.
@HeatingGeek
@HeatingGeek 4 жыл бұрын
No problem. Im glad it helped. :-)
@BenHallam
@BenHallam 5 жыл бұрын
Perfect mate. Just done mine. Exactly as you describe. The plastic nut turned to dust.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
The cheese nut turned to cheeeeeeeesseee. Good job.:-)
@alecburns8942
@alecburns8942 5 жыл бұрын
Love your vids, as a late starting 'Newbie setting up on my own, your vids help me put the knowledge into practice, thank you. You seem to have everything in your van no matter what's throw at you, can you (or anyone)recommend a van stock? Don't need consumables, hardware or tooling just to be able to turn up and do the job and not make a trip to the merchants all the time. Keep em coming
@HeatingGeek
@HeatingGeek 5 жыл бұрын
I cant really recommend a van stock as it depends what boilers you see. I see a lot of Vaillant and Worcesters so keep bits for them. Also I follow other engineers a lot so they will order parts for me to collect.
@assifkhan3803
@assifkhan3803 4 жыл бұрын
Thank good commentary and one handed experienced pluming well done
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Thanks. Its hart to film and do at the same time. :-)
@Ismail-Yahya
@Ismail-Yahya 4 жыл бұрын
One of the best plumber channels on KZfaq. Period!. You're doing a great job, keep em coming!
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Nice one. Thanks :-)
@madsmate7833
@madsmate7833 Жыл бұрын
Thanks mate..I usually avoid Worcester but it is a friend's boiler.. I was able to replace the adapter with confidence.. and you're right about the 'cheese' and need for a pick.. I enjoy your uploads and I'm learning all the time(33 years)😂
@HeatingGeek
@HeatingGeek 6 ай бұрын
MMM Cheese. The flow adaptors are shit.
@robgannon8285
@robgannon8285 Жыл бұрын
Well explained 👌 thank you 🙏
@gonzalomartinez1630
@gonzalomartinez1630 5 жыл бұрын
Thanks for sharing, we are at least glad the phone din't go in the bucket. I learn a lot from you.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Yep!!!! Could of been worse!!!
@tomwelch4204
@tomwelch4204 Жыл бұрын
Thank you brilliant video
@qomerhussain8176
@qomerhussain8176 Жыл бұрын
Hey, many thanks for this video. It helped diagnose the problem. Hopefully I will be able to get the part today amd fix the dripping water sorry to hear about your phone.
@HeatingGeek
@HeatingGeek 4 ай бұрын
Sorry I didn’t respond to this comment. I didn’t see it in my feed. :-(
@harrygibson3432
@harrygibson3432 5 жыл бұрын
Keep the vids coming!!
@HeatingGeek
@HeatingGeek 5 жыл бұрын
I will try. Its a bit busy at the moment!!!
@auntiemandy5638
@auntiemandy5638 5 жыл бұрын
i love that you charged them £3 for parts , what a Gent
@marcusbrookes7723
@marcusbrookes7723 5 жыл бұрын
Nice video , wish I had this video at hand the first time I did one
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Me too!! ;-)
@lezjones9751
@lezjones9751 3 жыл бұрын
Excellent help, saved myself £s. Bloody German cheese plastic in mine as well. Thanks for your help.
@RichardCarter-de7my
@RichardCarter-de7my Жыл бұрын
Thanks mate for the help and for showing us that black German cheese is useless for use in boilers
@HeatingGeek
@HeatingGeek 4 ай бұрын
Sorry I didn’t respond to this comment. I didn’t see it in my feed. :-(
@johnniewalker4931
@johnniewalker4931 4 жыл бұрын
I have an older model, without the green plastic cover over the diverter valve motor, and when the flow sensor/flow restrictor leaks the water goes onto the motor/actuator. This meant that the diverter valve actuator wasn't operating, and resulted in no CH, luckily I managed to repair it by just pulling out the diverter valve motor, dismantling it and then lubricating the seized bearing with WD40, this cured the problem and saved £50 for a new motor :)
@HeatingGeek
@HeatingGeek 4 жыл бұрын
I usually just shake the crap out of them and they start to work straight away. I have had to replace a few though. Great engineering the green cap. ;-/
@tomtate-dc2kd
@tomtate-dc2kd 4 жыл бұрын
Brilliant video and really informative. Just had one fitted today by gas safe guy. Did a cracking job. That part is so poorly made.
@HeatingGeek
@HeatingGeek 4 жыл бұрын
I know. Really poor quality plastic. Glad ypu got it sorted.:-)
@nabeelarshad78
@nabeelarshad78 5 ай бұрын
It was great help.. thanks
@HeatingGeek
@HeatingGeek 5 ай бұрын
No problem. :-) Are you doing one?
@enforcementofficer4802
@enforcementofficer4802 5 жыл бұрын
Great video - thanks :)
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Thanks. :-)
@simplemind7532
@simplemind7532 5 жыл бұрын
👊😎 great vid!
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Thanks for watching it. :-)
@heatservicebwcuk1545
@heatservicebwcuk1545 5 жыл бұрын
Alaways awkward ! That pin is a joke and why they didn’t re design that adaptor with brass is one reason I don’t fit Worcester unless I have to. I spoke to Worcester once and asked them why and there reason was cost ! To patch it up with the green rubber jacket over the diverter motor just says it all. Poor
@kopkings5
@kopkings5 2 жыл бұрын
Great video…thanks so much for sharing. Really helped. Unfortunately in my case it was still leaking after the change? Im pretty sure ive done something wrong but not sure where. Seems like i did everything the same as this vid. Is it normal for the sensor pipe to be put back in with full force while trying to at the same time insert the clip back in. This part was a nightmare for me and just as long as the the rest of the job. Which is why i was even more gutted when the leake didnt stop. Repeated the process for good measure but still leaked. One thing i didnt need to do was undo the bottom nut of the sensor pipe….didnt need to as the top part pulled out with a little twist and turn. Any advice from anyone would be much appreciated.
@ljppotter3158
@ljppotter3158 4 жыл бұрын
Great helps this cheers
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Glad it helps
@mehulkumarvpatel
@mehulkumarvpatel 3 жыл бұрын
Thanks very much.
@HeatingGeek
@HeatingGeek 3 жыл бұрын
You're welcome!
@cardioking
@cardioking 5 жыл бұрын
Thanks for sacrificing your phone screens for us!
@HeatingGeek
@HeatingGeek 5 жыл бұрын
I can fit new ones myself now!!! Its all because of youtube...
@gason6175
@gason6175 5 жыл бұрын
top man you will be fixing watches next
@dig405
@dig405 5 жыл бұрын
Great Video helped out my plumber to fix the exact same problem, on my greenstar 24i junior, CH works but hot water is tepid unless a slow flow, have to turn off CH to have a decent shower, diverter valve motor piston moves as it should, water doesnt cut out so he thinks the HE plate is ok, any ideas .Thanks
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Check flow rate and gas rate. Your answer is in the results of the tests.
@kopkings5
@kopkings5 2 жыл бұрын
Hi mate, would you be able to tell me where i can get a new flow sensor pipe? I am wondering now if while i forced it out i bent it…which is why i had so much trouble putting it back in and its still leaking. Cant seem to find one online.
@Carl-re6zb
@Carl-re6zb 5 жыл бұрын
Why the Gas Safety check after a non gas related part replacement bruv? Is it just part of your fixed price labour charge? Another great vid for those who have not come across these situations. keep up the good work. Always an informative view
@DunkiSTI
@DunkiSTI 3 жыл бұрын
Great Vid. Did one of those yesterday. Went in blind and guessed the manifold but no, will carry one of these in case now. Do prefer Baxi for repairing. so much space in the duos and new baxi 600 and 800's, Brass components rule.
@HeatingGeek
@HeatingGeek 3 жыл бұрын
Brass components do rule. But plastic crap pay the bills :-)
@DunkiSTI
@DunkiSTI 3 жыл бұрын
@@HeatingGeek yes very true.😂 Keep up the good work👍
@RossMcgowanMaths
@RossMcgowanMaths 6 ай бұрын
I did my flow manifold 2 years ago. Was quoted 400 quid. I bough the part for 25 quid and did it in 2 hours. If I were doing them regularly then I'd get it done in 1 hour. Today another crappy plastic leak. Was quote 150 quid.Bought the part for 5 quid. I recon 20 min job. As long as I'm not breaking into the gas line and all I'm doing is isolating water and the job is obvious then I'm good to go. Of course if you are unsure then pay a professional to come out.
@HeatingGeek
@HeatingGeek 6 ай бұрын
This part can be a pig. The clip can be a pain to get back in. Im sure I must mention it in the video. Remember you need to open up the combustion chamber to access anything so make sure you get it closed back up.
@DavidJones-or8ek
@DavidJones-or8ek 5 жыл бұрын
Thank you so much for this, the bit about the diverter valve switch was crucial to me as I couldn't understand why 2 faults had happened at the same time; the leak and (apparently) the diverter valve. Is there a way in which I could contribute to the cost of the replacement screen for your phone?
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Glad It made sense to you. Its common to happen. The iPhone is no more!!! Lost/stolen. Just keep watching and sub. :-) Thanks
@lordlazerath
@lordlazerath 4 жыл бұрын
Thankyou for this, still usefull, just saved me a wet night till landlord's decide.
@peesib
@peesib 5 жыл бұрын
Please, please can someone advise as to how I could go about doing a 2/3 day course just enough to identify problems, sort out water level etc...not a proper college course just an intense plumbing course, don’t mind paying at all. Will save loads in long run, seriously, I don’t think you’ll ever know how depressed I was feeling today until the ‘good’ (I hope) plumber turned up at 9pm.
@robgannon8285
@robgannon8285 Жыл бұрын
Love how you refer to the cheap German plastic as cheese 😄
@HeatingGeek
@HeatingGeek 5 ай бұрын
Its yummy ;-)
@NeathVideos
@NeathVideos 2 жыл бұрын
I’ve got a small leak from the screw that’s you turned to open the water feed to the boiler. Any ideas?
@jazzmiah8953
@jazzmiah8953 5 жыл бұрын
Hi mate got a question for u. Worcester greenstar 30i. Heating is fine but no hot water. I have diagnosed it as the diverter stuck in heating mode and or the dhw sensor. Any ideas or tips to confirm what the problem is? Thanks
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Test them. I have a video on how to test 3 wire flow sensors and the diverter is simple to look at. This is the flow sensor video. kzfaq.info/get/bejne/fZqSgpt-vte1e58.html I did have one on the worcester but never up loaded it and cant find it now.
@kevinkenny8943
@kevinkenny8943 5 жыл бұрын
Great vidoe especially the cheese
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Mmmmmmm Cheeeeese.
@jezlucas3878
@jezlucas3878 Жыл бұрын
Cheers dude
@HeatingGeek
@HeatingGeek Жыл бұрын
Glad you like it. Sorry for the late reply.
@jezlucas3878
@jezlucas3878 Жыл бұрын
@@HeatingGeek no need to apologise, busy time of year
@peesib
@peesib 5 жыл бұрын
Anyone know of plumbers like this honest, knowledgeable person in the BURNLEY area. Please respond.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Good luck. Hope you get it sorted.
@peesib
@peesib 5 жыл бұрын
Cheers buddy. A plumber has just left, he diagnosed it as the air pump? Will get it tomorrow for either £36 or £44 and charge £40 for labour. Does the diagnosis and cost seem fair?
@HeatingGeek
@HeatingGeek 5 жыл бұрын
@@peesib I don't even know what an air pump is on a boiler. Must be crossed wires on whats wrong. £40 for labour is very cheap.
@peesib
@peesib 5 жыл бұрын
Sorry, automatic air vent(no.43 on manual) I think as I’ve just seen it on the Worcester Greenstar 25i manual online. It had what looked like a nozzle head. That is what he said was cause of leakage. I just hope he can sort it out. Seriously, I just forget how much is available online as I was born in 1975 when I started working there was no internet so always been a technophobe. After watching a few of your vids today and reading comments, I am seriously thinking of attending a short course on boilers as it’s the most costly household item and between me, my brothers and sisters there’s always summat going wrong with the boilers, must be a family curse!
@HeatingGeek
@HeatingGeek 5 жыл бұрын
@@peesib For an AAV thats fair money. Hopefully he gets it sorted for you.
@keithmatthews9043
@keithmatthews9043 5 жыл бұрын
Have just fitted mixer taps in kitchen and have Worcester 28cdi boiler now diverter valve is constantly pushing against micro switch carnt understand why have bled system and even isolated the new taps but problem still remains anybody any ideas Thanks
@HeatingGeek
@HeatingGeek 5 жыл бұрын
If you turn the stopcock off to the house does it go back in?? Is the hot pipe under the boiler hot? If so you could have caused a leak under the floor or something. Let me know.
@06ssingh
@06ssingh 5 жыл бұрын
these small tips are very helpful. just this week i ended up changing a programmer because of the relay. i learnt this from your video thanks
@ArksE8
@ArksE8 5 жыл бұрын
Dude what about drake 🙈
@HeatingGeek
@HeatingGeek 5 жыл бұрын
What??
@heatservicebwcuk1545
@heatservicebwcuk1545 5 жыл бұрын
Yeah wtf lol who’s drake
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Heat Service bwc uk . Im still lost. Is it playing in the background or something??
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Heat Service bwc uk . I cant be assed to watch the video again!!!
@joedsaunders
@joedsaunders 4 жыл бұрын
Hi All, Our hot water has stopped today (Heating still works) noticed water dripping from the boiler and it's coming from here. Would this be why we have no hot water? I'm pretty handy, would this be a DIY job or do I need to get a professional in?
@HeatingGeek
@HeatingGeek 4 жыл бұрын
This repair requires the combustion chamber seal being broken. The boiler then needs the combustion setting up. This is definitely a job for the pros.
@MrKylebailey
@MrKylebailey 4 жыл бұрын
Great video, would have been good to show how you put the flow sensor clip back in though as for anyone doing this for their first time will take longer doing that then changing the part lol
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Your so right. :-). I need 2 hands to that. :-)
@thebincleaner
@thebincleaner 5 жыл бұрын
do I have to isolate the loop fill and house stop cock for this job as I'm willing to give it a go ?
@HeatingGeek
@HeatingGeek 5 жыл бұрын
To do it you have to open the combustion chamber so I cant help you. Its not a job you should attempt yourself. Please get someone to do it for you. Even qualified engineers struggle with replacing this part as it can be very difficult.
@kieranwims1976
@kieranwims1976 5 жыл бұрын
Good job. Little tip, next time either remove the diverter valve or cover it up to stop it failing when water drips on it. Also before you pull out the adapter wd40 the adapter and move it from side to side working the wd40 in. Less likely to fall apart when you try and take it out. 👍🏻
@keithwebster6164
@keithwebster6164 5 жыл бұрын
That is not advisable. If you squirt WD 40 into potable water connections you will contaminate the water supply and have broken water regulations.
@ef7480
@ef7480 4 жыл бұрын
Come on guys play nicely...
@andrewmclaren6189
@andrewmclaren6189 6 ай бұрын
Hi great video thank you my question my boiler is constantly making water and discharge through the PRV valve which I have replaced it is not the filling loop the cold water mains inside the boiler has condensation and with a screwdriver I can here water flowing with hot tap off in the house boiler is a greenslave oil burner
@HeatingGeek
@HeatingGeek 6 ай бұрын
Mains water is getting into the heating system somehow. Look for older filling loops left on the system. The condensation in the boiler points to the mains water continuously running through the boiler. This could be a manifold that has failed or the plate heat exchanger. I suggest you listen to these items. What is a green slave? Greenstar heatslave?
@andrewmclaren6189
@andrewmclaren6189 6 ай бұрын
@@HeatingGeek thank you I disconnected the filling loop so will listen to the others thanks again
@HeatingGeek
@HeatingGeek 6 ай бұрын
@@andrewmclaren6189 Good luck with it. I hope you get it sorted.
@LordJasonKing
@LordJasonKing 2 жыл бұрын
Can you use Vaseline instead of grease?
@dazdavison1
@dazdavison1 4 жыл бұрын
If that flow adaptor snaps on pulling it out how can i get the rest of it out
@HeatingGeek
@HeatingGeek 4 жыл бұрын
A screwdriver or a pick. I use a pick.
@dilaliotube
@dilaliotube 5 жыл бұрын
I fit Intergas not WB tupperware. Got booked on one of these junior poc's today and whish I'd watched this vid first. What a PITA! Changed the turbine adaptor only to discover return block had a pinhole and had to change the whole thing! Cut my hands to shreds and broke my phone screen just like you did grrrrrr.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Phone screens could be better TBH. Worcester are ok..... :-)
@dilaliotube
@dilaliotube 5 жыл бұрын
Lol. Nothing worse than having to work on/change parts in a boiler that my boiler of choice just doesn't have or need 😜
@Dr.Stacker
@Dr.Stacker Жыл бұрын
Did you replace the fibre washer on the pipe going to the mounting block? If so what size and PN? Thanks
@HeatingGeek
@HeatingGeek 4 ай бұрын
Sorry I didn’t respond to this comment. I didn’t see it in my feed. :-(
@paulwilliams8536
@paulwilliams8536 Жыл бұрын
Would this sensor be responsible for no hot water? I get preheated water from the hot tap for a minute or so then It goes cold
@HeatingGeek
@HeatingGeek Жыл бұрын
Yes it would. Sorry for the late reply.
@bobbob-hv6qs
@bobbob-hv6qs 4 жыл бұрын
is there an o ring at the front ????, as I have put one on and cannot get the clip back in as there is no room for the pin to go through, also I have tried with out but it just leeks
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Yes there is. Have you made sure all the old one is out? The front clip is a pig to get back in. :-) I couldn't get it in on camera. Its tough. :-)
@rw3095
@rw3095 4 жыл бұрын
So there is supposed to be an o ring at the front where it meets the plate? I wonder why the adapter only comes with 2 o rings in the pack? Looks like I'll be going back 😂
@HeatingGeek
@HeatingGeek 4 жыл бұрын
@@rw3095 Yes one behind the nut and one on the back. It is very difficult to get the clip back in after the parts go back together. :-)
@rw3095
@rw3095 4 жыл бұрын
The 1 i worked on had an extra o ring at the front of the turbine adaptor where it joins to the plate hex. Also the flow restrictors were missing. I'm guessing with the restrictors missing then it shortens the overall length of the flow turbine slightly and previous engineer had tried to compensate. Thanks
@nynono
@nynono 5 жыл бұрын
Hi ! Gas engineer from Romania here , any videos of Immergas / Ariston / Ferroli classic or condensing boilers ? Thanks and have a great day ! I can share things i've fixed during the 5 years of boiler service , if needed.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
no Intergas at the moment. If i get the chance I will film one.
@drpipe
@drpipe 5 жыл бұрын
I like the engineering of Wb...so that leaks and causes issues with the motor below...how to resolve ? Put a green cover over the motor that gets wet ! Genius ! Or Prv change...take the boiler off the wall ! And these are Which's best in show !
@HeatingGeek
@HeatingGeek 5 жыл бұрын
It keeps us in work.
@moulesanctuary
@moulesanctuary 3 жыл бұрын
They've started to put a boot over the divertor valve now to keep it dry .. another brill video
@petmister1
@petmister1 3 жыл бұрын
Have you ever had a flow sensor go faulty without any leaks?
@HeatingGeek
@HeatingGeek 3 жыл бұрын
yes,
@jamess5185
@jamess5185 5 жыл бұрын
another good vid mate , them retaining clips are nightmare little tip is you struggle with them file the tips at a slight angle as the go in better with a little tip have seen myself spend over an hour just on them clips usually when in a cupboard when boiler poor access
@gason6175
@gason6175 5 жыл бұрын
yes been there on that one lol
@Pro-nj4uu
@Pro-nj4uu 5 жыл бұрын
If you struggle to get that clip in there is a good chance the silencers are not fitted correctly in the adapter therefore the whole assembly is slightly proud which makes fitting the clip very difficult.
@paulkramer2599
@paulkramer2599 5 жыл бұрын
@@Pro-nj4uu ...Silencers !! ????
@nimasala8764
@nimasala8764 4 жыл бұрын
What’s the first things u did, close the main valve and the unscrew the pipe and run hot tap ? Is it for draining the boiler?
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Isolate the mains and open the hot tap. Then undo the nut and take out the clip. etc etc. :-)
@HeatingGeek
@HeatingGeek 4 жыл бұрын
When it's all back together the clip will be very difficult to get in.
@nimasala8764
@nimasala8764 4 жыл бұрын
@@HeatingGeek exactly, I'm spending an hour to put back the clip, any tip adv?
@ddoubledutch4783
@ddoubledutch4783 4 жыл бұрын
Nemo Sala I found putting the longest side of the clip in the right hand side first a little then just open it a little to push the left down into its hole. Worked a treat the times I’ve changed this part. Sorry if I pushed in with a suggestion there.
@HeatingGeek
@HeatingGeek 4 жыл бұрын
@@nimasala8764 welcome to the club. :-)
@valentinmirauta7059
@valentinmirauta7059 Жыл бұрын
A good lesson about cheese boiler
@adamwilliams5372
@adamwilliams5372 2 жыл бұрын
Had 2 of these in 2 days 😂
@heatservicebwcuk1545
@heatservicebwcuk1545 5 жыл бұрын
Mate my screen on my iPhone is shagged again too ! Had the phone just over a year aswell this will be 3rd cannot be arsed to keep changing them now ! Always use it a a torch and end up dropping it. Can’t they make a screen that won’t break !
@HeatingGeek
@HeatingGeek 5 жыл бұрын
They can but that would be like making a boiler that didn't leak!!! No jobs for us and Worcester wouldn't sell any flow adaptors. (Vaillant wouldn't sell diverters etc etc).
@heatservicebwcuk1545
@heatservicebwcuk1545 5 жыл бұрын
Very true. whether Worcester designed that part to fail I don’t know. Ecotec diverters like wise At the price it sells for I wouldn’t think it would be worth tarnishing reputation for something that is so cheap cost wise. Then again high volumes of failures even at 2 quid profit is still good business for them. Flow adaptors that is.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Heat Service bwc uk Yeah its pretty bad really. You think they would update stuff and move the issue onto other bits. (Vaillant). The diverter has leaked since 2004 and still leeks alll the time.
@paulkramer2599
@paulkramer2599 5 жыл бұрын
@@HeatingGeek have you tried any of the non-Vaillant repair kits for the ecotec diverter valves yet ?
@HeatingGeek
@HeatingGeek 5 жыл бұрын
@@paulkramer2599 Yes I have. I have a video coming soon about them. I done the filming before Christmas........
@bluedwarf8858
@bluedwarf8858 4 жыл бұрын
I've changed the same part, the way Worcester make their boilers baffles me, cheap parts that once become faulty are a bit time consuming to change.
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Yes, its a strange thing on a "premium" boiler...
@keithmatthews9043
@keithmatthews9043 5 жыл бұрын
Hi have turned stopcock off diverter valve still pressing against micro switch when taps turned on boiler lights and hot water is there, central heating has now gone . I need to turn boiler off at mains electric each time I use hot water cus heating pump gets really hot 🥵 even when boiler not fired.another mystery. Have had local plumber round had he’s sure it’s the diverter valve. Thanks
@HeatingGeek
@HeatingGeek 5 жыл бұрын
If its still out when the stopcock is off then its the diverter. The pump is getting red hot because its running forever (because of the diverter). Good luck hope it goes well.
@keithmatthews9043
@keithmatthews9043 5 жыл бұрын
HeatingGeek hi thanks for your reply I have ordered a diverter valve but at same time its nice to have reassurance of a professional I will fit it when I get it.i did it about 2years ago but only replaced the diaphragm so I am hoping it will come apart a bit easier thanks again
@keithmatthews9043
@keithmatthews9043 5 жыл бұрын
Have now subscribed to your channel 👍
@HeatingGeek
@HeatingGeek 5 жыл бұрын
@@keithmatthews9043 good luck. They can be a pig!!
@HeatingGeek
@HeatingGeek 5 жыл бұрын
@@keithmatthews9043 Thanks. You know these comments are on a video of a Greenstar. I guess your talking about a CDi RSF. Im sure thats where we started talking!!!
@belialuedke1880
@belialuedke1880 5 жыл бұрын
Sweet. 😇
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Thanks. :-)
@adamwilliams5372
@adamwilliams5372 2 жыл бұрын
The new cheese is there 😂 quality
@sucksqueezebangblow5248
@sucksqueezebangblow5248 4 жыл бұрын
What grease did you use please?
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Silicone grease.
@joboeyful
@joboeyful 2 жыл бұрын
You legend. Never would of guess that fucking o ring goes behind the thread !!!
@SuperCkpatel
@SuperCkpatel 3 жыл бұрын
how much part cost
@michaelcole4010
@michaelcole4010 4 жыл бұрын
hi how much would you charge for this job....
@HeatingGeek
@HeatingGeek 4 жыл бұрын
I charge a fixed fee for labour for any repair.£150 plus parts. So the total cost would be 170
@adamsala9291
@adamsala9291 5 жыл бұрын
Superb again what type grease do you use.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
This is the exact stuff I use. I didn't know how expensive it was!!!! Silicone grease amzn.to/2Rnls4F
@adamsala9291
@adamsala9291 5 жыл бұрын
👍 exspensive thnx.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
@@adamsala9291 Im sure you can get smaller tubes or cheaper stuff.
@whitebear5405
@whitebear5405 4 жыл бұрын
Why is the first comment always I hate Worcester. I've never had any issue that I couldn't easily fix on a Worcester you guys just got to do the training. Piece of cake when you know how
@HeatingGeek
@HeatingGeek 4 жыл бұрын
All boilers are easy once you have done them a few times. Worcester are sharp and cut your hands to bits if you're not careful. :-)
@iftakharmohammed1942
@iftakharmohammed1942 4 жыл бұрын
Worcester should include spare free flow sensor and return manifold and flow manifold included in the box when they send the boiler out from the factory.
@HeatingGeek
@HeatingGeek 4 жыл бұрын
So much plastic cheese in that boiler. Keeps us busy though. :-)
@dimiretail1546
@dimiretail1546 5 жыл бұрын
Where's the pink rag? Great video. £3 for parts, outstanding.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Pink rag was there Im sure. Just a cameo for it on this one. Easy job this. except the clip.
@mike004692
@mike004692 5 жыл бұрын
Just done one today , £5.41 from Parts Center
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Thats too expensive. :-)
@peterhamriding7739
@peterhamriding7739 5 жыл бұрын
i would strongly advise anyone who fits Worcester boilers to fit a shock arrester on the mains inlet to reduce problems with poor quality manifolds and flow reducers .
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Or fit a Vaillant that don't seem to have the poor plastic issue.
@r8cha
@r8cha 5 жыл бұрын
Hiya Pete... just randomly spotted you hear! 😄
@mickelsmickle8668
@mickelsmickle8668 4 жыл бұрын
How do we know it's The flow sensor leaking
@HeatingGeek
@HeatingGeek 4 жыл бұрын
It's not usually the flow sensor. Usually the flow adaptor behind the sensor.
@mickelsmickle8668
@mickelsmickle8668 4 жыл бұрын
@@HeatingGeek ok will write that down
@dr.usman83
@dr.usman83 4 жыл бұрын
The clip is a pain... can’t seem to get it in properly ..
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Yes, it is. Has to go at a slight angle to get it in. ;-0
@darrenhooper3457
@darrenhooper3457 5 жыл бұрын
hate that metal retaining clip with a passion..I always fit a green cover onto the stepper motor it has a slope on it to let the water run off!!! pure quality
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Its like they know its a problem. ;-)
@darrenhooper3457
@darrenhooper3457 5 жыл бұрын
HeatingGeek I stand corrected I fitted a service kit to a baxi 80he instant diverter section/bypass onto the vessel today it was has to be the worst design ever
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Darren Hooper. The one with the two pipes onto the vessel? I cant ever remember doing one. Probably blocked it out!!!
@woodbine66
@woodbine66 5 жыл бұрын
Those Wooshitter Botch boilers and their cheap plastic parts. But, the boilers aren't cheap to buy - much more than other better boilers. The customers always say "Which Magazine always rates them highly". Hmm. Thanks for another excellent one, HG.
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Thanks :-)
@garlictyme2472
@garlictyme2472 2 жыл бұрын
I need one of those in USA, and it costs $310. I might just get an electric water heater.
@k20aa
@k20aa 5 жыл бұрын
That Bin was nearly Big enough to throw all that heap of crap straight in there
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Yep. LOL Customer over reaction.
@toooldtodieyoungmotorcyle
@toooldtodieyoungmotorcyle 5 жыл бұрын
Great video just mended mine with exactly the same problem. The irony is of course when you realise the German cheese you mention is actually made yep you guessed it "The United Kingdom."
@HeatingGeek
@HeatingGeek 5 жыл бұрын
Is it? Grunfoss make the manifolds I think.
@nindes
@nindes 3 жыл бұрын
Can't get the clip back on and that why im here grrrr
@HeatingGeek
@HeatingGeek 3 жыл бұрын
Its on by now I hope. :-) Let me know
@paulscurfield
@paulscurfield 4 жыл бұрын
Overpriced plastic shite. great vid!
@HeatingGeek
@HeatingGeek 4 жыл бұрын
I see you are enlightened. :-)
@mickelsmickle8668
@mickelsmickle8668 4 жыл бұрын
As have same boiler and everything day large amount of water leaks out in one gush not condense trap I am a gas engineer also but not as skilled as you
@HeatingGeek
@HeatingGeek 4 жыл бұрын
Do you have to top up the pressure? Where does it look like it coming from?
@mickelsmickle8668
@mickelsmickle8668 4 жыл бұрын
@@HeatingGeek the pressure is always low but it still cool works even after I top it up it goes down in a few days not sure where coming from havnt checked to be honest to busy doing everyone else boilers 😁
@HeatingGeek
@HeatingGeek 4 жыл бұрын
@@mickelsmickle8668 Maybe the vessel leaks at the seam or the PRV isnt in the slip joint correctly. :-)
@mickelsmickle8668
@mickelsmickle8668 4 жыл бұрын
@@HeatingGeek can't thank you enough you are q real star and you now have a student and a fan for life watching your videos I have learnt so much I listen to them while driving top man giving your time and experience for free 👊🏼👊🏿👊🏿 big respect to you brother I mean that wish you all the success
@HeatingGeek
@HeatingGeek 4 жыл бұрын
@@mickelsmickle8668 Glad you like it. Thanks for letting me know. :-)
Worcester Greenstar Return manifold
28:16
HeatingGeek
Рет қаралды 10 М.
Engineer Runs Away from Overheating Boiler.
13:55
HeatingGeek
Рет қаралды 42 М.
Smart Sigma Kid #funny #sigma #comedy
00:40
CRAZY GREAPA
Рет қаралды 8 МЛН
Slow motion boy #shorts by Tsuriki Show
00:14
Tsuriki Show
Рет қаралды 9 МЛН
ВОДА В СОЛО
00:20
⚡️КАН АНДРЕЙ⚡️
Рет қаралды 30 МЛН
Flow Turbine adapter change on a Worcester Bosch
5:41
CP Utility Solutions
Рет қаралды 35 М.
Worcester Bosch 30si/28i junior flow adaptor replacement
8:53
Boilers To Bathrooms
Рет қаралды 6 М.
"Step-By-Step" Boiler Repair
21:40
HeatingGeek
Рет қаралды 14 М.
How To: Boiler Losing Pressure
15:40
HeatingGeek
Рет қаралды 6 М.
Heating Hacks: How to Safely Unblock A Cold Feed Pipe
16:25
HeatingGeek
Рет қаралды 10 М.
Why Does My Boiler Keep Losing Pressure?
36:37
Skill Builder
Рет қаралды 393 М.