Looks a very technical job but im sure its not too bad once you have done a few of them.not for the faint hearted.very well explained.
@BoilerMend5 ай бұрын
Thank you 🫶
@Carl-re6zb8 ай бұрын
Epic rebuild brother
@user-li8gr8ur8l3 ай бұрын
That is quite some info to take in. ❤😂. Top video buddy
@BoilerMend2 ай бұрын
Thank you 🫶
@BoilerMend2 ай бұрын
Think this sort of extensive information is useful, possibly once before and while carrying out such work. You can only remember this info, if you replace these main heat exchangers, somewhat regularly.
@douglaughton76263 ай бұрын
I have a job to replace this very same today. Thank you for your video. I now have confidence. The fault u had on this boiler. I would have x800 it on hot water only withf&r isolated. My job, it’s leaking thru condensate drain
@BoilerMend3 ай бұрын
👌
@melvinevans9981 Жыл бұрын
Well done, bro. I hope I never have to change one, lol Great work man
@BoilerMend Жыл бұрын
😂😂
@BoilerMend Жыл бұрын
It's not too bad.. A Lot better than some other Worcesters. And yes, you get better after doing a few.. 👍
@SAS-gu9kl8 ай бұрын
Good work mate 👍 🎉 ps see ya at the break fast meeting 👍 😂😂😂😂 next month 😂😂😂
@BoilerMend8 ай бұрын
🤫.. Oo Dis? 🤔
@SAS-gu9kl8 ай бұрын
@@BoilerMend u will never guess 🤣🤣🤣🤣 u can run but u can't hide 😉
@ohmz558 ай бұрын
New engineer here. When a main heat exchanger gets blocked, is the boiler not creating enough heat (50-60degrees) a common symptom? I thought they would over heat and then modulate down. Tks
@BoilerMend8 ай бұрын
Hi. First of all, apologies for the late reply. So, the main hx can cause both issues. If it's blocked real bad, it'll overheat and Lockout or cutout. Secondly, if it part blocked, water will still be able to circulate through it, but as debris are occupying part of the heating space inside the main hx, it won't let out much or little heat. Hope this addresses your query 😬
@paulsmith2931 Жыл бұрын
What’s that boiler about 12 years old, price of the hex and given other age problems with them like the plastic manifolds leaking, flow turbine adapter, I’d have gone down the road of a new boiler.
@BoilerMend6 ай бұрын
👍
@kamaldahal46728 ай бұрын
Good job, how much to charge for the job like this plz